AirCooled Aftercoolers

Why use this equipment?
This equipment is a heat exchanger to cool the compressed air discharged from an air compressor with atmospheric air.
The compressed air is cooled to approximately 9oC, above ambient temperature. This substantially reduces the water and level of other contaminants in the air-supply, as water will be reduced by 1/2 for every 20 degree reduction in temperature.
Sizing Notes, Recommendations are based on the following :-
Heat Removal : After cooler = Compressor horsepower x 1.15 ( motor service factor ) x .17 (this assumes 17% of input horsepower is rejected to heat).
15oF Approach Temperature : Compressor air outlet temperature - ambient air temperature.
Temperatures : Ambient Air Temperature + 15oF = Compressed Air Outlet Temperature.
Flows : Compressor Horsepower x 4.5 = SCFM Air Flow.
Air flow rates are based on less than a 4 PSI pressure drop @ 100 PSI operating & 100oF ambient and 50% relative humidity
Ratings :
Maximum working pressure : 250psi
Maximum working temperature : 250oF
Materials:
Cooler : Aluminum
Shroud : Powder Painted Steel.
Fan guard : Zinc Plated Steel.
Fan Blade : Polypropylene Blades Aluminum Hub.
Mounting brackets : Powder Painted Steel.